Core & Coil (71A) MH ~LT~ 175W

CORE & COIL HID MH BAL 100W M90/140 480V/120T C&C

CORE & COIL HID MH BAL 100W M90/140 480V/120T C&C

  • Reliable performance

    Product information

    Downloads

    Leaflet
    Size:936.8 kB

    See all downloads

Videos

[trigger to render Video Gallery]

Images

Specifications Show all

General Information
ANSI Code
M90-M140
Lamp Type
100 MH
Number of Lamps
1 piece/unit
Circuit Type
HX-HPF
Ballast Type
Magnetic HID
Base Model
71A5340T
Core Size
3 X 4 (2 coil)
Suitable For Outdoor Use
Yes
Ignitor Catalog Number
LI533-H4
Ignitor Temperature Rating
105°C
Capacitor Value
10 MFD
Capacitor Catalog Number
7C100M30RA
Capacitor Requirements
300V
Capacitor Temperature Rating
105°C
Capacitor Diameter/Oval Dimensions
1.65 in
Capacitor Height
2.75 in
Automatic Restart
No
Operating and Electrical
Input Voltage
480 V
Input Frequency
60 Hz
Inp. Current (Open Circuit)
0.55 A
Input Current (Starting)
0.3 A
Input Current (Short Circuit)
0.24-0.36 A
Secondary Short Circuit Current
1.35-1.65 A
Constant Wattage Deviation
12%
Ballast Factor (Nom)
1
Power Factor (Nom)
0.90
Nominal Open Circuit Voltage
260 V
Input Current (Operating) (Nom)
0.3 A A
Input Power (Nom)
132 W
Rated Lamp Watts
100W W
Wiring
Wire Striplength
0.5 mm
Wire Length By Color
12"
Wire Type
Stranded
Remote Wiring Configuration Allowed
Yes
Max Ballast-Lamp Distance Remote Wiring
25'
Recommended Fuse Value
2 A
Approval and Application
Open Circuit Voltage Test (Volts)
234-286 V
Temperature Marking
C
UL Recognized
Yes
Hipot Test (1 Minute)
2000 V
Hipot Test (2 Seconds)
2500 V
UL Insulation Class
H(180°C)
UL Temperature Code
1029C
Product Data
Order product name
CORE & COIL HID 71A5340510DT
EAN/UPC - Product
781087101209
Order code
71A5340510DT
Numerator - Quantity Per Pack
1
Numerator - Packs per outer box
4
Material Nr. (12NC)
913710488202
Net Weight (Piece)
2.663 kg

Eco passport - Our environmental product specifications overview

Philips cares about the environment and society at large, and strongly supports eco-design of products.

Installation Diagrams

Recently Viewed

  • Share this page
    • Manage your projects with MyProjects
      Use MyProjects to create, save manage and share items and projects with you colleagues and team members.
You are now visiting our Global professional lighting website, visit your local website by going to the USA website